Whole-home heat loss calculator
Estimate whole-home design heat loss from assessed fabric and ventilation heat transfer.
After you calculate
See your home design heat loss
Add your assessed fabric and ventilation heat-transfer coefficients and design temperatures, then calculate to see your results.
Design heat loss
Shown after calculationHeat transfer total
Shown after calculationFabric heat loss
Ventilation heat loss
Full calculation
Uses assessed heat-transfer coefficients in W/K and your indoor and outdoor design temperatures.
Understand your estimate
How it works
Work out whole-home design heat loss from assessed fabric and ventilation heat transfer. Fabric heat transfer describes heat passing through parts of the building. Ventilation heat transfer describes heat carried out by air movement. Both inputs need to come from a property assessment or a suitable measured study.
Enter the two heat-transfer figures in watts per kelvin, shown as W/K. Add the indoor and outdoor design temperatures used in that assessment. The result is the heating power needed for those stated conditions. It is not an estimate made from floor area, the age of the home or a typical household energy bill.
A few good questions
Before youget started.
Understand this calculator, the figures to enter and the limits of your estimate.
Sources
- Energy Saving Trust: heat-transfer and design heat-loss assessmentChecked on 14 October 2026
- Last checked
- 14 October 2026
EnergySums
Whole-home heat loss calculator
United Kingdom · How it works
- Guide updated
- 14 October 2026
| Item | Value |
|---|---|
| Guide updated | 14 October 2026 |
How it works
Work out whole-home design heat loss from assessed fabric and ventilation heat transfer. Fabric heat transfer describes heat passing through parts of the building. Ventilation heat transfer describes heat carried out by air movement. Both inputs need to come from a property assessment or a suitable measured study.
Enter the two heat-transfer figures in watts per kelvin, shown as W/K. Add the indoor and outdoor design temperatures used in that assessment. The result is the heating power needed for those stated conditions. It is not an estimate made from floor area, the age of the home or a typical household energy bill.
Formula
Whole-home heat transfer = fabric W/K + ventilation W/K. Design heat loss kW = total W/K × (indoor − outdoor °C) ÷ 1000.
A heat-transfer coefficient is the number of watts lost for each degree of temperature difference. A one-degree Celsius difference is the same size as one kelvin. Subtract outdoor temperature from indoor temperature, then multiply by the combined coefficient. Divide watts by 1000 to express the answer in kilowatts.
The result is power, rather than energy used over a year. Kilowatts, written kW, describe a rate of heat loss at the entered temperatures. Kilowatt-hours, written kWh, include time. This tool does not multiply the design loss by every hour in a year or convert it into a heating bill.
Check the substituted working against the assessment. Make sure the fabric and ventilation figures cover the same building. Adding a whole-home measured total as fabric heat transfer and then adding ventilation again would count part of the heat loss twice.
Worked example
These illustrative inputs are separate from your saved answers. Prices, use and performance are held constant for this worked scenario; they are not personal defaults.
Inputs used in this worked example.
- Assessed fabric heat transfer
- 180 W / K
- Assessed ventilation heat transfer
- 20 W / K
- Indoor design temperature
- 20 °C
- Outdoor design temperature
- -5 °C
| Item | Value |
|---|---|
| Assessed fabric heat transfer | 180 W / K |
| Assessed ventilation heat transfer | 20 W / K |
| Indoor design temperature | 20 °C |
| Outdoor design temperature | -5 °C |
- Whole-home design heat loss
- 5 kW
- Total heat transfer
- 200 W/K
- Temperature difference
- 25 °C
| Item | Value |
|---|---|
| Whole-home design heat loss | 5 kW |
| Total heat transfer | 200 W/K |
| Temperature difference | 25 °C |
- Whole-home design heat loss
- (180 + 20) W/K × (20 − -5) K ÷ 1,000 W/kW= 5 kW
| Calculation | Formula with saved values | Result |
|---|---|---|
| Whole-home design heat loss | (180 + 20) W/K × (20 − -5) K ÷ 1,000 W/kW | 5 kW |
Assumptions and limits
The coefficients must come from a professional assessment or measured heat-transfer study with its stated uncertainty. No assumed wall, air-change or floor-area value is supplied. Blank fields stay empty; an example does not become a property measurement.
The chosen indoor and outdoor temperatures define this scenario. Changing the temperature difference changes the result while the entered coefficients stay fixed. That is an arithmetic comparison, rather than a weather forecast or proof of how the home performs in every condition.
This is not a room-by-room radiator design, a heat-loss survey or a heat pump sizing certificate. It does not check emitter output, equipment performance or installation suitability. Money and energy prices are not used. Display values are rounded, but the calculation uses unrounded numbers. An invalid edit keeps the last valid snapshot visible with a warning.
Country rules
Use a documented assessment for the UK property being considered. Keep its units, building boundary and design conditions with the entered figures. A source explaining the heat-loss method does not supply the missing measurements for your home.
The checked dates identify the stored method records. They do not show that your property has been surveyed or that a particular design has been approved. If an assessment uses different terms, ask its author which figures match the two coefficient fields. Do not substitute an energy bill or equipment rating for a heat-transfer coefficient.
When to ask a professional
Ask a qualified heating professional when you do not have matching coefficients or need room-by-room design work. Bring the assessment, its assumptions and the chosen temperatures. Ask whether its fabric figure excludes ventilation so the two entries can be added safely.
Before choosing equipment, have an installer check the property, emitters and available heat output at the design conditions. This calculation can help explain the assessed total, but it cannot certify performance, safe installation or compliance with local requirements.
Questions and answers
| Question | Answer |
|---|---|
| Where do I get heat-transfer coefficients? | Use a professional fabric and ventilation assessment or an appropriately measured whole-home heat-transfer study. A floor area or property age alone is not a coefficient. |
| Can I use this to size individual radiators? | A whole-home total does not allocate heat loss between rooms or check emitter performance. Ask a heating engineer for the room and system assessment. |
| Does the result equal a heat pump nameplate rating? | Ask the installer to match equipment output to the relevant outdoor and heating-water design conditions. A nominal rating at different conditions is not a confirmed match. |
| Why must indoor temperature be higher? | This tool estimates outward heat loss for a heating design condition. Equal or reversed temperatures do not represent that scenario and must be corrected. |
Sources
| Source | Checked | Reference URL |
|---|---|---|
| Energy Saving Trust: heat-transfer and design heat-loss assessment | 14 October 2026 | https://greenheattoolkit.energysavingtrust.org.uk/t/heat-pump-installers-toolkit/heat-pump-system-design/heat-loss-calculations-detailed-guidance/ |